Wholesale Data Center Liquid Cooling Pipes from JILAIDA, a professional Special Shaped Stainless Steel Seamless Tube manufacturer in China. We work from your cross-section, coolant spec and pressure class, then return tooling feasibility, a written quote and lead time the same working day.
Product Features
Our tube is a seamless hot-extruded profile — no weld seam, no heat-affected zone, no corner joint. That structure lets us hold wall thickness and bore finish where a welded tube cannot.
- Seamless unequal-wall extrusion, e.g. 3.3 / 3.3 / 3.3 / 13 mm
- Alloy matched to coolant: 304, 316, C276, N06625, HC-22
- Bore finish to Ra 0.8 µm for immersion loops
- Pressure-rated wall for two-phase and primary-side duty
- Full-penetration UT on seamless sections on request
Where It Is Used
We supply Data Center Liquid Cooling Pipes for all five architectures running in production today; the wall and alloy change with each loop. We size the section to the loop's temperature, chemistry and pressure, not to the server vendor.
| Architecture | What the tube must deliver |
|---|---|
| Cold plate | Tight internal Ra, predictable flow at 25–40 °C, deionized water or low-concentration PG |
| Single-phase immersion | Secondary loop, 316 for chloride trace, 0.8 µm bore finish |
| Two-phase immersion | Higher pressure rating, thicker base wall, full-penetration UT |
| Rear-door heat exchanger | Compact OD, equal-wall rectangular profile, push-fit or threaded end prep |
| Spray cooling | Nozzle-grade dimensional control, bore free of laps or oxide inclusions |
How We Select the Alloy
Coolant chemistry drives the grade, not the architecture. Our engineers read the loop and specify accordingly:
- 304 — sealed loop, 10–30% PG, below 50 °C
- 316 — above 40% glycol, above 50 °C, or dielectric fluid with trace chloride
- C276 / N06625 / HC-22 — brazed exchanger with copper or aluminium on the secondary side
Inspection and Documents
Every length of Data Center Liquid Cooling Pipes ships with an EN 10204 3.1 MTC covering chemistry, mechanical properties and dimensional inspection. SGS, BV or TÜV third-party witness is available on request, and we ship FOB, CIF or DDP, factory-direct from China.
FAQ
Q1: One spec or two across the CDU?
Two. The secondary side is usually 304, 3.3/3.3/3.3/13 mm; the primary side is 316 with a thicker base wall and tighter bore. We quote both Data Center Liquid Cooling Pipes specs on one purchase order.
Q2: Is the standard MTC enough, or do we need witness?
Standard MTC covers most projects. SGS or BV third-party witness is available when your QA plan requires it.
Q3: The loop shows trace copper from exchanger brazing — does that change the alloy?
Yes. We move the spec to C276 or N06625 to remove the copper–stainless couple, holding the same wall and Ra.